Insulation R-Value Thickness Calculator

Insulation R-Value Thickness Calculator

Estimate the required insulation thickness to reach a target R-value based on material R-value per unit thickness.

Choosing a material will auto-fill R-value per inch. You can still edit it manually.
Desired overall R-value for the insulated assembly.
Example (imperial): R per inch. Example (metric): R per cm.

What the insulation R-value thickness calculator does

The insulation R-value thickness calculator tells you how thick a layer of insulation has to be to reach a target R-value. Pick a material from the preset list or enter the R-value per inch yourself, type the total R-value you want, choose inches or centimetres, and press Calculate. The result is the required thickness in the chosen unit with the metric or imperial equivalent alongside.

The formula

thickness = target R-value ÷ R-value per unit thickness

R-values add in proportion to thickness, so the calculation is a simple division. With the default target of R-30 and 3.5 per inch: 30 ÷ 3.5 = 8.6 inches, or 21.8 cm.

R-value per inch of common materials

MaterialR per inch (imperial)Inches for R-30Notes
Fiberglass batt3.29.4Cheapest; loses value if compressed
High-density fiberglass3.78.1Used where cavity depth is limited
Cellulose loose-fill3.87.9Recycled paper; settles 10 to 20% over time
Mineral wool4.07.5Fire resistant, holds shape
Rigid foam board (XPS / polyiso)5.06.0Polyiso is higher when new, lower when cold
Closed-cell spray foam6.05.0Also an air and vapour barrier

The presets set the R-per-inch field automatically. Product labels give the declared figure for the actual batch, which should replace the preset when you have it.

Typical target R-values

LocationCold climate (IECC zones 5 to 7)Mild climate (zones 2 to 3)
Attic / ceilingR-49 to R-60R-38
Wood-frame wallR-20 to R-21 cavity plus R-5 continuousR-13 to R-15
Floor over unheated spaceR-30R-13 to R-19
Basement wallR-15 continuousR-5 or none

For an attic at R-49 with blown cellulose: 49 ÷ 3.8 = 12.9 inches. With loose-fill, add the manufacturer’s settled-thickness allowance so the value holds after a few years.

When the cavity is too shallow

A 2×4 wall is 3.5 inches deep, which holds R-11 to R-13 of fiberglass or R-21 of closed-cell spray foam. A 2×6 wall (5.5 inches) holds R-19 to R-21 in fiberglass or R-23 in mineral wool. When the target exceeds what the cavity can hold, add continuous rigid foam on the outside of the studs; this also cuts thermal bridging through the framing, which otherwise reduces the whole-wall value by 20 to 30% below the cavity figure.

Imperial and metric R-values

North American R-values are in ft²·°F·h/BTU. The SI equivalent, m²·K/W, is 5.678 times smaller: R-30 imperial is RSI 5.3. European products quote thermal conductivity λ in W/m·K instead; R per metre is 1/λ, so mineral wool at λ = 0.035 gives RSI 2.86 per 100 mm, which converts to R-16 imperial per 100 mm, or about R-4.1 per inch. The thermal resistance calculator works from λ and thickness directly, and the U-value calculator turns a total R into the U-value used in European regulations.

Common mistakes

  • Entering RSI as an imperial R-value. A target of “5” meant as RSI needs to be entered as 28.4.
  • Compressing batts to fit. An R-19 batt squeezed into a 3.5 inch cavity delivers about R-13.
  • Counting nominal rather than settled thickness for loose-fill.
  • Ignoring air leakage. Insulation slows conduction; gaps around it let air carry heat straight through. Air sealing usually matters as much as thickness.

Related tools

The Fourier heat transfer calculator converts the finished R-value into heat loss in watts, and the heat flux converter switches units. For the rest of the job, the drywall sheets calculator and paint calculator estimate finishing materials, and the roof rafter length calculator helps size an attic retrofit.

External references

Frequently asked questions

Does doubling thickness double the R-value?

Yes for the insulation layer itself. Whole-assembly gains are smaller because framing, air films and cladding do not change.

Which material gives the most R-value per inch?

Vacuum insulated panels (R-25 to R-40 per inch) and aerogel (R-10) top the list but are expensive. Among common products, closed-cell spray foam and polyiso board lead at R-6 to R-6.5 per inch.

Is there a point where more insulation stops paying off?

Yes. Heat loss is proportional to 1/R, so going from R-10 to R-20 halves the loss, but R-40 to R-50 cuts only a further 20%. Code minimums are set near the economic optimum.

How do I convert R-value per inch to lambda?

λ (W/m·K) = 0.1442 ÷ R per inch. Fiberglass at R-3.2 per inch is λ = 0.045.

Does the calculator include air films or existing layers?

No. It sizes the insulation layer alone. Subtract the R-value of existing materials and surface films from the target before entering it.