Thermal Resistance Calculator

Thermal Resistance Calculator

What the thermal resistance calculator does

The thermal resistance calculator tells you how strongly a flat layer of material resists conductive heat flow. Enter the layer thickness in metres and the material’s thermal conductivity in W/(m·K), press Calculate, and the tool returns the thermal resistance R in m²·K/W. The higher the value, the better the layer insulates.

The formula

R = d / k

  • d is the thickness of the layer in metres
  • k is the thermal conductivity in watts per metre-kelvin
  • R is the thermal resistance per unit area, in m²·K/W

This is the R-value used in building physics. Doubling the thickness doubles the resistance; halving the conductivity does the same. Thermal resistance is the reciprocal of the U-value for a single layer, so you can move between the two with the U-value calculator.

Thermal conductivity of common materials

Materialk (W/m·K)R for 100 mm (m²·K/W)
Copper4000.00025
Steel450.0022
Concrete1.70.059
Brick0.70.14
Softwood timber0.130.77
Plasterboard0.250.40
Mineral wool0.0382.6
Expanded polystyrene (EPS)0.0362.8
Polyurethane foam0.0254.0
Still air0.0263.8 (in theory, before convection)

Values are typical at room temperature. Manufacturers publish declared conductivity for specific products; use those figures for real projects.

Worked examples

Wall insulation. 150 mm of mineral wool with k = 0.038: R = 0.150 / 0.038 = 3.95 m²·K/W.

A concrete slab. 200 mm of concrete with k = 1.7: R = 0.200 / 1.7 = 0.118 m²·K/W. The same slab with 100 mm of polyurethane underneath adds 4.0, so the floor’s total resistance rises to about 4.1 m²·K/W.

A heatsink base. A 5 mm aluminium plate (k = 205): R = 0.005 / 205 = 0.0000244 m²·K/W. Metals contribute almost nothing to resistance; in electronics the interface materials and the air side dominate.

Layers in series

For a wall made of several layers, calculate each R separately and add them: Rtotal = R1 + R2 + R3 + … Surface resistances are added as well; standard values are 0.13 m²·K/W for the inside face and 0.04 m²·K/W for the outside face of a wall. A typical cavity wall might be: outer brick 0.14, cavity 0.18, mineral wool 2.6, block 0.11, plaster 0.06, plus surfaces 0.17, for a total near 3.3 m²·K/W and a U-value of about 0.30 W/m²·K.

From resistance to heat flow

Once you have R, the conductive heat flux through the layer is q = ΔT / R in W/m², where ΔT is the temperature difference across it. For the 150 mm mineral wool example with 20 °C inside and 0 °C outside, q = 20 / 3.95 = 5.1 W/m². A 40 m² wall loses about 200 W. The Fourier heat transfer calculator does this step directly.

Imperial R-values

North American product labels use ft²·°F·h/BTU. Multiply the SI value by 5.678 to convert. R = 3.95 m²·K/W is R-22 in imperial units. The insulation R-value thickness calculator works in the other direction: it tells you how thick a layer must be to reach a target R.

Common mistakes

  • Entering thickness in millimetres. 100 mm is 0.1 m. The calculator expects metres.
  • Using the resistance of a bare material for a product. Foil facings, air gaps and compression change the effective value.
  • Ignoring thermal bridges. Studs, fixings and mortar joints conduct heat around the insulation and reduce the real average resistance.
  • Applying the formula to convection or radiation. R = d/k is for conduction through a solid only. Use the Nusselt number calculator for convective coefficients.

Related tools

The thermal conductivity converter switches between W/m·K and BTU·in/(h·ft²·°F). The heat flux converter handles W/m² and BTU/h·ft². For sizing heating equipment against the losses you calculate, see the boiler size calculator.

External references

Frequently asked questions

What is a good thermal resistance for a wall?

Modern codes in cold climates call for total wall resistances of roughly 3 to 5 m²·K/W (U-values of 0.2 to 0.3 W/m²·K). Roofs are usually required to reach 5 to 7 m²·K/W.

Is thermal resistance the same as R-value?

Yes. R-value is the everyday name for thermal resistance per unit area. In the SI system the unit is m²·K/W; in the imperial system it is ft²·°F·h/BTU.

How is thermal resistance related to U-value?

U = 1 / Rtotal. A total resistance of 4 m²·K/W is a U-value of 0.25 W/m²·K.

Does temperature affect the result?

Thermal conductivity rises slightly with temperature for most insulation, by a few percent between 10 °C and 40 °C. Use the conductivity declared at the mean temperature of your application when precision matters.

Can I use this for a pipe?

Not directly. Cylindrical layers need the logarithmic form R = ln(r₂/r₁) / (2πkL). The flat-layer formula is a reasonable approximation only when the insulation is thin compared with the pipe radius.